Athena C10 line Manuale Utente Pagina 3

  • Scaricare
  • Aggiungi ai miei manuali
  • Stampa
  • Pagina
    / 4
  • Indice
  • SEGNALIBRI
  • Valutato. / 5. Basato su recensioni clienti
Vedere la pagina 2
Features
at Env. 25°C
Common
characteristics
From keypad or serial communications, the user selects:
- the type of input - the type of output and the safe conditions
- the associated functions and the - the type and functionality of the alarms
corresponding outputs - the values of all the control parameters
- the type of control algorithm
A/D converter with 50,000 points
Update measurement time : 0.2 sec
Sampling time : 0.5 sec
Input shift : ± 60 digits
Input filter : 1...30 sec (OFF= 0)
Accuracy
0.25% ± 1 digit (T/C and RTD)
0.1% ± 1 digit (mA* and mV)
Resistance
thermometer
(for T: R1+R2
must be <320)
Pt100 at 0°C
(IEC 751)
°C /°F
selectable
2 or 3 wire
connection
Line: 20max (3 wire)
Thermal drift
0.35°C/10°C env. T.
<0.35°C/10 line
resist.
Thermocouple
L,J,T,K,S
(IEC 584)
°C /°F
selectable
Internal cold
junction
compensation
Line: 150 max
Thermal drift
<2µV/°C env. T.
<5µV/ line resist.
DC input
(current)
0/4...20mA
with 2.5 ext.
Shunt
Rj > 10M
Engineering units,
floating decimal point,
Low Range -999...9999
High Range -999...9999
100 digits minimum
Input drift:
< 0.1%/20°C env. T.
DC input
(voltage)
0/10…50mV
Rj >10M
Indicator
with 2 alarms
AL1 alarm AL2 alarm
OP1- relay or triac OP2 - Logic
OP2 - Logic OP1 - relay or triac
1 PID loop or ON/OFF
with 1 alarm
Control output AL2 alarm
OP1 - relay or triac OP2 - Logic
OP2 - Logic OP1 - relay or triac
Algorithm P.I.D. with overshoot control or ON/OFF
Proport. band (P) 0.5…999.9%
P.I.D. algorithm
Integral time (I) 0.1…100.0 min.
OFF = 0
Derivative time (D) 0.01…10.00 min.
Cycle time 1…200 sec.s
Overshoot control 0.01…1.00
High limit 100.0…10.0%
Hysteresis 0.1…10.0% ON/OFF algorithm
SPST relay N.O., 2A/250V~ for resistive load
Triac, 1A/250V~ for resistive load
Logic (SSR drive) not isolated: 5V
, ± 10%, 30mA max
Between 100 and
240V
~error is
minimal
Total
configurability
Process
Variable (PV)
input
(for signal
ranges
see Table 1)
Operating
modes
Control mode
Output 1 (OP1)
Output 2 (OP2)
Hysteresis 0.1…10.0% range
Active high
Absolute threshold, whole range
Active low
Hysteresis 0.1…10.0% range
Action
Action
type
Deviation threshold ± range
Band threshold 0…range
Absolute threshold, whole range
Sensor break
Up and down ramps 0.1…999.9 digit/min (OFF = 0)
Low limit from low range to high limit
High limit from low limit to high range
Galvanically isolated: 500V~/1min
Resolution: 12 bit (0.025%)
Accuracy: 0.1%
Current output:
0/4...20mA 750/15V max
Depending on the process condition,
the controller applies the best method
Step response
Natural frequency
RS485 isolated, Modbus/Jbus protocol 1200, 2400, 4800, 9600 bit/sec, two wires
+18V
±20%, 30mA max for external transmitter supply (Option)
Alarm 1 (AL1)
(indicator with
2 alarms)
Alarm 2 (AL2)
Setpoint
(Option)
PV retransmission
output
One-shot
F
uzzy
tuning
Ser. comms. (opt.)
Aux. p. supply
Input Type
RTD
Pt100 at 0°C
T/C type L
Fe-Const.
T/C type
J
Fe-Cu 45% Ni
T/C type
T
Cu - CuNi
T/C type
K
Chromel- Alumel
T/C type
S
Pt10%Rh-Pt
0/4…20 mA
0/10…50 mV
Configurable engineering units
mA, mV, V, bar, psi, RH, pH
0…1600 °C
32…2912 °F
0…1200 °C
32…2192 °F
-200…400 °C
-328…752 °F
0…600 °C
32…1112 °F
0…600 °C
32…1112 °F
-99.9…300.0 °C
-99.9…572.0 °F
-200…600 °C
-328…1112 °F
Scale Range
Table 1 : Process Variable (PV) Inputs/Signal Ranges
Fuzzy Tuning
Two methods of tuning are available:
- Auto-Tuning (one-shot)
- Natural Frequency (one-shot)
Fuzzy Tuning automatically selects one of the two
methods which ensure the best result for each
condition.
The Auto-Tuning method works best on the step
response basis. When activated, if a deviation
exists between the setpoint and process variable
larger than 5% of scale range, the controller
modifies the output value. Then, in a short time, it
calculates the P.I.D. parameters and the new
algorithm is operational immediately. The main
advantages of this method are fast calculation
and quick implementation.
The Natural Frequency method works best when
the process variable is very near to the setpoint.
When activated, it causes a process oscillation
around the setpoint value. The main advantage of
this method is a reduced disturbance to the
process.
SP
Tuning end time and
parameter setting
Auto-tuning start
Setpoint change
PV
Main control
output
PV
Main control
output
Natural frequency
tuning start
Tuning end time and
PID parameter setting
3
Active high
Active low
Special function
Description
Technical Data
*Requires field calibration for 0.1% accuracy
Vedere la pagina 2
1 2 3 4

Commenti su questo manuale

Nessun commento